Model resolution

Electricity-onlySector-coupledOvernightMyopicPerfect foresight

The resolution of the model is a choice in three dimensions: how many regions, how many hours, and which sectors and carriers should be modelled. Finer resolution captures more of the grid, the weather and the regional variety of demand, but the optimisation problem grows with every dimension. This page explains what the resolution settings do so that the trade-off can be made deliberately 12.

Spatial resolution

Base regions

The starting point is the topology of the European high-voltage transmission network, built from OpenStreetMap by default or, alternatively, from the ENTSO-E reference grid of the Ten-Year Network Development Plan. It contains the substations, AC lines and cables, HVDC links with their converters, and transformers across all synchronous areas of the ENTSO-E region. Planned transmission projects can be added on top. How the grid is derived from OpenStreetMap data is described under Electricity.

Every substation defines a base region: the area that is closer to this substation than to any other, cut at country borders so that national totals stay intact. The areas around the substations are built as Voronoi cells and are the catchment areas for demand, renewable potentials and power plants. Whatever lies in a cell is assumed to connect to its substation. Offshore regions are built the same way from the exclusive economic zones (EEZs) and the nearest coastal substations.

Onshore regions of the base network

Simplification and clustering

Solving a capacity expansion problem for thousands of substations is out of reach due to its computational complexity. So the network complexity is reduced in two steps, simplification and clustering:

Simplification brings all lines to one voltage level, removes dead-end branches by attaching their resources to the neighbouring node, and collapses chains of converters and links into single connections. Nothing is lost that matters for planning at continental scale.

Clustering aggregates the simplified network to the requested number of regions 3. Several modes exist:

  • Algorithmic clustering groups substations within each country, by k-means on electricity demand, by hierarchical agglomerative clustering on weather features, or by greedy modularity on the grid topology, so that clusters correspond to load and generation centres.
  • Administrative clustering uses statistical regions such as countries, NUTS levels or bidding zones as clusters.
  • Custom clustering takes a user-provided assignment of substations to regions or a set of region shapes.

The lines between clustered regions inherit the aggregated electrical characteristics of the original lines. Their cost includes a detour factor over the straight-line distance, and for HVDC links the fraction running underwater. Selected regions can also be declared copperplated, that is without any transmission constraints inside them.

Exemplary clustered networks with few and many regions

The clustered electricity regions are the regions of all other carriers too. There is one set of regions for the whole model. The grid below transmission level is not represented topologically; each region has one optimised link between transmission and low-voltage level, see Electricity.

Which carriers are resolved regionally

Not every carrier is worth resolving at the same detail. Electricity, heat and hydrogen are always nodal because their transport is either expensive or technically constrained. For other carriers the model offers a choice between one node for all of Europe and full regional resolution:

Carrier Regional resolution
Electricity, heat, hydrogen always nodal
Methane optional; with the gas transmission network
Solid biomass optional; with transport costs between regions
Carbon dioxide optional; with a CO2 pipeline network
Oil products, methanol optional demand resolution; supply copperplated
Ammonia optional

A single node is a reasonable simplification where future demand is small compared to existing transport capacity or where transport is cheap, as for liquid fuels. Regional resolution matters where infrastructure decisions are the research question, for example whether a hydrogen backbone or a CO2 network should be built.

Temporal resolution

The model optimises over the hours of one or several weather years. Weather data comes from the ERA5 reanalysis 4 and the SARAH satellite irradiation record 5, processed with atlite 6 into so-called cutouts. The year of demand and weather can be chosen freely, and multi-year runs are possible by extending the snapshot range. Which weather year is chosen matters, since the variability between years is large 7.

To reduce solving time, the hourly snapshots can be aggregated before optimisation:

  • Averaging merges consecutive hours into blocks of equal length.
  • Segmentation merges consecutive hours into blocks of variable length, chosen so that the time series of demand and renewable availability are represented as well as possible.
  • Representative snapshots keep every n-th hour and scale its weight.

Aggregation is applied uniformly to all time series in the model, so that supply and demand remain consistent. Multi-period planning across investment years is described under Foresight.

Sectoral resolution

The third dimension is which sectors and carriers are in the model at all. The electricity-only model contains the electricity system alone. The sector-coupled model adds heating, transport, industry and agriculture as sectors, and hydrogen, ammonia, methane, oil, methanol, biomass and carbon dioxide as carriers. Each sector can be switched off individually, in which case its demand and its technologies are simply absent. Within a sector, the detail is adjustable as well: the five heat systems per region can be merged to three, the ammonia carrier can be collapsed into hydrogen and electricity demands, and optional technologies such as methanol-to-power or aquifer storage are added only when enabled.

Fewer sectors mean a smaller problem but also fewer interactions. Sector coupling matters for the electricity system mainly through the flexibility that heat pumps, electric vehicles and electrolysers add, and through the demand they place on the grid 8. The overview lists which features exist in which variant.


  1. Jonas Horsch and Tom Brown. The role of spatial scale in joint optimisations of generation and transmission for European highly renewable scenarios. In 2017 14th International Conference on the European Energy Market (EEM), 1–7. IEEE, 2017. doi:10.1109/EEM.2017.7982024. ↩

  2. Martha Maria Frysztacki, Jonas Hörsch, Veit Hagenmeyer, and Tom Brown. The strong effect of network resolution on electricity system models with high shares of wind and solar. Applied Energy, 291:116726, 2021. doi:10.1016/j.apenergy.2021.116726. ↩

  3. Martha Maria Frysztacki, Gereon Recht, and Tom Brown. A comparison of clustering methods for the spatial reduction of renewable electricity optimisation models of Europe. Energy Informatics, 5(1):4, 2022. URL: https://energyinformatics.springeropen.com/articles/10.1186/s42162-022-00187-7, doi:10.1186/s42162-022-00187-7. ↩

  4. Hans Hersbach, Bill Bell, Paul Berrisford, Shoji Hirahara, András Horányi, Joaquín Muñoz-Sabater, Julien Nicolas, Carole Peubey, Raluca Radu, Dinand Schepers, Adrian Simmons, Cornel Soci, Saleh Abdalla, Xavier Abellan, Gianpaolo Balsamo, Peter Bechtold, Gionata Biavati, Jean Bidlot, Massimo Bonavita, Giovanna De Chiara, Per Dahlgren, Dick Dee, Michail Diamantakis, Rossana Dragani, Johannes Flemming, Richard Forbes, Manuel Fuentes, Alan Geer, Leo Haimberger, Sean Healy, Robin J. Hogan, Elías Hólm, Marta Janisková, Sarah Keeley, Patrick Laloyaux, Philippe Lopez, Cristina Lupu, Gabor Radnoti, Patricia de Rosnay, Iryna Rozum, Freja Vamborg, Sebastien Villaume, and Jean-Noël Thépaut. The ERA5 global reanalysis. Q. J. R. Meteorol. Soc., 146(730):1999–2049, 2020. doi:10.1002/qj.3803. ↩

  5. Uwe Pfeifroth, Steffen Kothe, Richard Müller, Jörg Trentmann, Rainer Hollmann, Petra Fuchs, and Martin Werscheck. Surface radiation data set - heliosat (SARAH) - edition 2. 2017. doi:10.5676/EUM_SAF_CM/SARAH/V002. ↩